CHEMICAL CLEANING OF BOILER IS CARRIED OUT IN THREE CONDITION :-
- BEFORE INITIAL START OF BOILER.
- IN CASE OF HEAVY OIL CONTAMINATION.
- IN CASE OF HEAVY SCALING OR CORROSION.
ALKALINE BOILING OUT IS CARRIED OUT BY TRI-SODIUM PHOSPHATE OR CAUSTIC SODA 2500 PPM EACH. THIS IS CARRIED OUT IN CASE OF OIL CONTAMINATION OF BOILER WATER.
PROCEDURE:-
- FILL WATER TO NORMAL LEVEL WITH FEED WATER USED FOR REGULAR SERVICE. WATER SHOULD BE DEAERATED.
- CHEMICAL USED FOR BOILING OUT SHOULD BE COMPLETELY DISSOLVED BEFORE THEY ENTER THE UNIT AND FED BY CHEMICAL FEED CONNECTION.
- START FIRING THE BOILER SLOWLY.
- PRESSURE TO BE RAISED SLOWLY AND AT CONSTANT RATE TILL 3.5 TO 4 BAR MINIMUM.
- BOILER TO BE BLOWDOWN AT LEAST ONCE EVERY 8 HOURS DURING BOILING OUT.
- HALF OF GAUGE GLASS TO BE BLOW DOWN TOTALLY AND DIVIDED EQUALLY IN ALL MAIN BLOW DOWN.
- AT END OF BLOW DOWN , WATER IS BROUGHT BACK TO SAME LEVEL AS NORMAL AND REPLENISHED WITH CHEMICAL TO PROPER CONCENTRATION.
- TO BE DONE TILL NO CONTAMINATION ARE PRESENT IN WATER SAMPLE FROM BLOW DOWN LINES.