WITH THE DETECTOR FITTED , ELECTRICALLY CONNECTED, FUNCTIONING AND CONFIGURED, COMMENCE THE SMOKE ALARM TEST AS FOLLOWS :-
A) CUT A LENGTH OF WICK OF ABOUT 30 MM LONG. ASSEMBLE THE SMOKE TESTER BY PUSHING THE WICK INTO THE WICK HOLDER FITTED WITH THE PIPETTE BULB.

B) PUSH THE NYLON PIPE OF THE SMOKE TESTER INTO THE CONNECTOR ON THE SIDE OF THE DETECTOR BASE BODY.

C) DIP THE WICK INTO THE BOTTLE OF SMOKE OIL AND RESEAL THE BOTTLE FIRMLY.
D) IGNITE THE WICK OF THE SMOKE TESTER AND BLOW OUT THE FLAME. SQUEEZE THE PIPETTE BULB TO KEEP THE WICK SMOKING.
E) WHILE THE WICK IS STILL SMOULDERING, INSERT IT INTO THE PIPE CONNECTOR AND SQUEEZE THE PIPETTE BULB.
F) OBSERVE THE LIGHT CHANGE THE STATE. THE RED LIGHT SHOULD COME ON ALONG WITH THE GREEN LIGHT, TO INDICATE AN ALARM. FAILURE OF THE RED LIGHT TO COME ON MAY BE DUE TO THE WICK NOT SMOULDERING, RELIGHT IF NECESSARY.
G) TO RELEASE THE PIPE FROM THE PIPE CONNECTOR, PRESS IN THE BLUE PLASTIC COLLAR ON THE END OF THE CONNECTOR AT THE SAME TIME AS PULLING THE PIPE OUT.
H) REMOVE THE NYLON PIPE FROM THE PIPE CONNECTOR FOR STOWAGE PURPOSE.
I) THE WICK IS REUSABLE AND CAN BE LEFT IN THE WICK HOLDER. FULLY EXTINGUISH THE WICK AFTER USE AT ALL TIME.